- 1. AAC material is approximately one third to one quarter of the weight of conventional concrete, which reduces cost of the foundation by quantity savings in concrete and steel.
- 2. Slab on grade is to be higher than external finished ground level land so that wall panel does not get in contact with soil.
- 3. PAC Panels (VP) are reinforced for load bearing applications. Table below shows permissible compressive stress on vertical wall panels (VP) based on ACI codes. And table below show the maximum length of VP & HP with various design lateral loads.
Permissible Compressive Stress (Newton/mm2) for the walls.
WALL HEIGHT (mm) |
Thickness (mm) |
100 |
150 |
200 |
250 |
300 |
2500 | - |
0.62 |
0.91 |
1.10 |
1.10 |
2750 | - |
0.48 |
0.83 |
1.02 |
1.10 |
3000 | - |
0.36 |
0.74 |
0.96 |
1.10 |
3500 | - |
- |
0.55 |
0.81 |
0.98 |
4000 | - |
- |
- |
0.66 |
0.86 |
4500 | - |
- |
- |
- |
0.74 |
5000 | - |
- |
- |
- |
0.62 |
Maximum Length of Wall Panels with various lateral loads
THICKNESS (MM) |
Maximum Hight of Wall Panels with different design wind load |
0.8 kN/m |
1.4 kN/m |
2 kN/m |
2.6 kN/m |
100 |
3000 mm |
3000 mm |
2500 mm |
|
150 |
4500 mm |
4000 mm |
3500 mm |
3000 mm |
200 |
6000 mm |
6000 mm |
6000 mm |
6000 mm |
250 |
6000 mm |
6000 mm |
6000 mm |
6000 mm |
300 |
6000 mm |
6000 mm |
6000 mm |
6000 mm |
Lintels are used as load bearing members over window and door openings for external or interior walls, Table below shows the maximum clear span of lintels in cm with design load mm for.
DESIGN LOAD (kN/m) |
Maximum span of lintel with different Load and Thickness with fixed load of 600 mm |
100 mm |
150 mm |
200 mm |
250 mm |
300 mm |
5 |
2500 |
4500 |
4500 |
5400 |
6000 |
10 |
2000 |
3250 |
4000 |
4500 |
5000 |
15 |
1000 |
2750 |
3250 |
3750 |
4100 |
PAC slabs attain their design strength during the high – pressure steam curing process in the autoclaves. Thus slabs can be erected and ready for use immediately after delivery to the site. Slabs are reinforced with double steel welded mesh and anticorrosion coated.
FS & RS slabs are produced in various thickness and spans depending on the required load bearing capacities. The table below shows the permissible spans in mm with different design loads.
SUPERIMPOSED LOAD |
| SLABS THICKNESS |
(KG/m2) |
100 mm | 150 mm |
200 mm |
250 mm |
300 mm |
250 |
2850 | 4450 |
5850 |
6000 |
6000 |
300 |
2650 | 4250 |
5500 |
6000 |
6000 |
350 |
2550 | 4000 |
5150 |
6000 |
6000 |
400 |
2450 | 3800 |
5000 |
6000 |
6000 |
450 |
2350 | 3500 |
4800 |
5650 |
6000 |
500 |
2250 | 3500 |
4600 |
5650 |
6000 |
550 |
2000 | 3350 |
4450 |
5450 |
6000 |
600 | 1850 | 2950 | 4150 | 5250 | 6000 |
650 | 1700 | 2700 | 3800 | 4800 | 5900 |